Malfunctions of the control if the control is
switched off while updating.
Ensure that, depending on the software variant, "HW init" is displayed after
switching on the control. Wait unit the procedure is completed (approx. 20
seconds). Do not switch off the control. Within this period, an update is
running. This procedure has to be completed. Subsequently, continue com-
missioning.
5. If necessary, use a lithium battery for the optional SRAM memory, see also
chapter 5 "Spare parts, accessories and wear parts" on page 6 and chap-
ter 14.4 "Lithium battery" on page 45
6. If necessary, make other settings (IP address, subnet mask, gateway ad-
dress, ...) at the display. For further information, please refer to the de-
scription of the relevant system (MLC, IndraLogic, MTX, MLC, XLC).