RE 30126-01-B/08.07 | Manual Hydraulics | Bosch Rexroth AG 20/76
Application: Valve control for the 4WRE6 / 4WRE10 3
Configure Analog I/O - Inputs
The following parameters can be used to configure the Analog I/O – Inputs:
The value range of the signal in [%] is set in the „Range“ column. If the selection +/-
10V is made in the „Type“ column a signal of (-10V) corresponds to a signal of (-
100%) when the range setting is +/-100%.
The „Min“ value sets the minimum fort he input signal. Depending on the setting of
„Type“ and „Range“ this value is translated to the minimum value of the „Range“
setting.
If for example you enter -5V , with Type = +/-10V and Range = +/- 100%, a signal of -
5V is interpreted as -100%.
The „Max“ setting is the opposite of the „Min“. If +9V is entered a signal of +9V is
interpreted as 100%.
If the value falls below the entered value, BODAC uses the „Status“ window and the
„Status bar“ to indicate that a fault has occurred. Specifying the error response is
done in the “Faults” window.
If the value exceeds the entered value, BODAC uses the „Status“ window and the
„Status bar“ to indicate that a fault has occured. Specifying the error response is done
in the “Faults” window.
The „max Unit“ specifies the conversion from Range [%] to Units [Unit].
Fields that can not be modified are grayed-out.
Range
Min
Max