Rockwell Automation Publication D2-3518-4 - January 2020 129
Parameter Descriptions Chapter 9
Present frequency reference scaled as a DPI reference for peer-to-peer
communications. The value shown is the output prior to the accel/decel ramp
and any corrections supplied by slip comp, PI, etc.
Present frequency reference scaled as a DPI reference for peer-to-peer
communications. The value shown is the value after the accel/decel ramp but
prior to any corrections supplied by slip comp, PI, etc.
Enables and disables control of the drive by particular DPI devices or the digital
inputs.
Figure 60 - Logic Mask (276)
Bits
(1)
Description
14 13 12
0
0
0
0
1
1
1
1
0
0
1
1
0
0
1
1
0
1
0
1
0
1
0
1
No Command - Man. Mode
Ref A Auto
Preset 2 Auto
Preset 3 Auto
Preset 4 Auto
Preset 5 Auto
Preset 6 Auto
Preset 7 Auto
272
Drive Ref Rslt
Range: -/+32767 [1]
Default: Read Only
Access: 1 Path: Communication > Comm Control
See also:
273
Drive Ramp Rslt
Range: -/+32767 [1]
Default: Read Only
Access: 1 Path: Communication > Comm Control
See also:
276
Logic Mask
Range: See Figure 60
Default: See Figure 60
Access: 1 Path: Communication > Masks & Owners
See also: 288...297
100000xxxxxxxxxx
0011234567891112131415
1 =Control Enabled
0=Control Disabled
x =Reserved
Bit #
Digital In
DPI Port 1
DPI Port 2
DPI Port 3
DPI Port 4
DPI Port 5
Nibble 1Nibble 2Nibble 3Nibble 4
Factory Default Bit Values