Rockwell Automation Publication D2-3518-4 - January 2020 135
Parameter Descriptions Chapter 9
Parameters that can be changed only while the drive is stopped cannot be used as
Datalink inputs. Entering a parameter of this type disables the link.
Refer to the appropriate communications option board manual for datalink
information.
Parameter number whose value is written from a communications device data
table.
Parameters that can be changed only while the drive is stopped cannot be used as
Datalink inputs. Entering a parameter of this type disables the link.
Refer to the appropriate communications option board manual for datalink
information.
Parameter number whose value is written to a communications device data table.
Parameter number whose value is written to a communications device data table.
306
307
Data In D1 - Link D Word 1
Data In D2 - Link D Word 2
Range: 0...387 [1]
Default: 306 = 34
307 = 35
Access: 1 Path: Communication > Datalinks
See also:
IMPORTANT In Liquiflo 2.0 drives, datalink D is used for inverter/rectifier communication.
Do not change these two parameters.
310
311
Data Out A1- Link A Word 1
Data Out A2 - Link A Word 2
Range: 0...387 [1]
Default: 0 (Disabled)
Access: 1 Path: Communication > Datalinks
See also:
312
313
Data Out B1- Link B Word 1
Data Out B2 - Link B Word 2
Range: 0...387 [1]
Default: 0 (Disabled)
Access: 1 Path: Communication > Datalinks
See also: