136 Rockwell Automation Publication D2-3518-4 - January 2020
Chapter 9 Parameter Descriptions
Parameter number whose value is written to a communications device data table.
Parameter number whose value is written to a communications device data table.
Selects the type of input signal being used for user-configurable analog inputs
1 and 2.
Figure 64 - Anlg In Config (320)
For Frame 4 drives only (firmware version 2.x), the actual modes of the analog
inputs depend on the value of this parameter and on the capabilities of the analog
input hardware on the Combined I/O board. The units (V or mA) displayed for
the Analog In Hi and Analog In Lo parameters are an accurate indication of the
actual mode of the corresponding analog input if the input is physically present
on the Combined I/O board.
314
315
Data Out C1- Link C Word 1
Data Out C2 - Link C Word 2
Range: 0...387 [1]
Default: 0 (Disabled)
Access: 1 Path: Communication > Datalinks
See also:
316
317
Data Out D1- Link D Word 1
Data Out D2 - Link D Word 2
Range: 0...387 [1]
Default: 316 = 33
317 = 218
Access: 1 Path: Communication > Datalinks
See also:
IMPORTANT In Liquiflo 2.0 drives, datalink D is used for inverter/rectifier communication.
Do not change these two parameters.
320
Anlg In Config
Range: See Figure 64
Default: See Figure 64
Access: 0 Path: Inputs & Outputs > Analog Inputs
See also: 322, 323, 325, 326
00xxxxxxxxxxxxxx
0011234567891112131415
1 =Current
0=Voltage
x =Reserved
Bit #
Factory Default Bit Values
Analog In 1
Analog In 2
Nibble 1Nibble 2Nibble 3Nibble 4