Rockwell Automation Publication D2-3518-4 - January 2020 137
Parameter Descriptions Chapter 9
See AC Line I/O Board Description (Frame 3 Only) on page 25 through
Combined I/O Board Description (Frame 4 Only)
on page 29 for a description
of I/O hardware that is present on this drive and is controlled by the inverter.
Enables/disables the square root function for each user-configurable analog
input.
See AC Line I/O Board Description (Frame 3 Only)
on page 25 through
Combined I/O Board Description (Frame 4 Only)
on page 29 for a description
of I/O hardware that is present on this drive and is controlled by the inverter.
This function should be enabled if the input signal varies with the square of the
quantity (for example, drive speed) being monitored. The square root function is
scaled such that the input range is the same as the output range. For example, if
the input is set up as a unipolar voltage input, then the input and output ranges of
the square root function are 0...10 volts.
Figure 65 - Anlg in Sqr Root (321)
The drive scales the value read from the user-configurable analog input and
converts it to units usable for the application. You control the scaling by setting
parameters that associate a low and high point in the input range with a low and
high point in the target range.
Analog In 1 Hi sets the highest input value to the user-configurable analog input
1 scaling block. See AC Line I/O Board Description (Frame 3 Only)
on page 25
through Combined I/O Board Description (Frame 4 Only)
on page 29 for a
321
Anlg In Sqr Root
Range: See Figure 65
Default: See Figure 65
Access: 1 Path: Inputs & Outputs > Analog Inputs
See also: 320, 322, 323, 324, 325, 326, 327
322
Analog In 1 Hi
Range: 4.000...20.000 mA [0.001 mA]
-/+10.000V [0.1V]
0.0...10.000V [0.1V]
Default: 20.000 mA
Access: 0 Path: Inputs & Outputs > Analog Inputs
See also: 91, 92, 320
xxxxxxxxxxxxxx
0
0
0
011234567891112131415
1 =Enable
0=Disable
x =Reserved
Bit #
Factory Default Bit Values
Analog ln 1
Analog ln 2
Nibble 1Nibble 2Nibble 3Nibble 4