Rockwell Automation Publication D2-3518-4 - January 2020 75
Parameter Descriptions Chapter 9
Figure 31 - Appl Digital Output (30) Frame 4
In addition to controlling digital output 3, bit 1 is also used to force the Aux Run
digital output condition to true. This only occurs if the Digital Out Sel
parameter for one of the user-configurable digital outputs is set to Aux Run.
The value entered into this parameter is output on the analog output when it is
configured for Application control. See parameter Analog Out1 Sel (342).
The usable range and default for this parameter depends on the operational mode
of the analog output, which in turn depends both on the capabilities of the analog
output hardware and the current value of parameter Analog Out Config (340).
Tab le 6
describes the details for usable range and default.
Table 6 - Appl Analog Output (31) usable range and default
The value in the Default column of Ta b le 6 is in effect when the drive powers up.
This parameter value is not stored in non-volatile memory.
For frame 3 drives (firmware version 1.x), the user-configurable analog output
hardware is located on the optional Standard I/O Board. This parameter is not
usable if the optional Standard I/O Board is not present. See Standard I/O Board
Description (Frame 3 Only) on page 27 for terminal block assignments.
31
Appl Analog Out
Range: -32.767...32.767 [0.001 mA, or 0.001V (frame 4 only)]
Default: See Table 6 below.
Access: 1 Path: Monitor > Application
See also: 342, 343, 344
Mode Usable Range Default
0...10V (unipolar) 0.000...10.000V 0.000V
-10...10V (bipolar) -10.000...10.000V 0.000V
4...20 mA 0.000...20.000 mA 0.000 mA
00000xxxxx
0011234567891112131415
1 =Active
0=Inactive
x =Reserved
Bit #
Shunt trip
Comb. I/O Dig. Output 3
Comb. I/O Dig. Output 4
Comb. I/O Dig. Output 5
Comb. I/O Dig. Output 6
Comb. I/O Dig. Output 7
Comb. I/O Dig. Output 8
Nibble 1Nibble 2Nibble 3Nibble 4
0
0
xx
Close Pre-charge
Enable Rectifier
0
0
Powerup Default Bit Values