Rockwell Automation Publication 750-RM004A-EN-P - April 2018 43
Selection Considerations Chapter 1
IEEE 519 AC input drives not compliant.
DC input drives with appropriate low
harmonic bus supply converter may
be compliant
(s) PowerFlex 755TL/TR
PowerFlex 755TM common bus
inverter with appropriate PowerFlex
755TM bus supply converter.
REACH — Regulation (EC) No. 1907/2006
concerning the Registration,
Evaluation, Authorization and
Restriction of Chemicals (REACH)
Packaging Directive — In conformity with the Packaging
Directive (94/62/EC and
amendments 2004/12/EC and 2005/
20/EC)
Table 12 - Protection Features
Description PowerFlex 700S, Frames 9…14 PowerFlex 755TL/TR Drive and
PowerFlex 755TM Common Bus
Inverter, Frames 8…12
Cat. No. 20D… Cat. No. 20G…
AC Input DC Input 755TL/TR 755TM CBI
AC Input Over Voltage Trip 400/480V; 675V
AC
600/690V; 889V
AC
— 400/480V; 542V AC
600/690V; 780V AC
—
AC Input Under Voltage Trip
Nominal value, adjustable and
configurable action
400V Class;
246V AC
480V Class;
295V AC
600V Class;
369V AC
690V Class;
424V AC
— 400V Class; 348V AC
480V Class; 418V AC
600V Class; 522V AC
690V Class; 600V AC
—
DC Bus Over Voltage Trip 400/480V Class; 911V DC
600/690V Class; 1200V DC
400/480V Class; 815V DC
600/690V Class; 1172V DC
DC Bus Under Voltage Shutdown/
Fault
Nominal value, adjustable and
configurable action
400V Class; 348V DC
480V Class; 417V DC
600V Class; 522V DC
690V Class; 976V DC
400V Class; 453V DC
480V Class; 543V DC
600V Class; 678V DC
690V Class; 781V DC
Heat Sink Temperature Fault (s) over temperature (s) over and under temperature
Ground Fault (s) (s)
Single Phase / Phase Loss Fault (s) — (s) —
Line Sync Fault — (s) —
Drive Overload Fault (s) (s)
IGBT Over temp Fault (s) (s)
LCL Filter Over temp Fault — (s) —
DC Bus Over Voltage Fault (s) (s)
Table 11 - Certifications and Standards Compliance
Description PowerFlex 700S, Frames 9…14 PowerFlex 755TL/TR Drive and
PowerFlex 755TM Common Bus
Inverter, Frames 8…12
Cat. No. 20D… Cat. No. 20G…