14 Safety input and command status (TEST mode)
;MXLRSGYVVIRXP]EGXMZIGSQQERHWTVIWWXLI8)78FYXXSRERHGLIGOXLIJSPPS[MRK
DISPLAY POSSIBLE CAUSE ACTION BY SOFTWARE
PHYSICAL CORRECTIVE
ACTION
 
The safety STOP contact is open.
-
Install a STOP button (NC) or jumper
the ST contact with the COM con-
tact.
 
Sensing edge COS1 not connected
or incorrectly connected.
Set the parameter  if not used
or to disable.
Jumper contact COS1 with contact
COM, if not used or to disable
 
Sensing edge COS2 not connected or
incorrectly connected.
Set the parameter  if not used
or to disable.
Jumper contact COS2 with contact
COM, if not used or to disable.
 
Photocell FT1 not connected or incor-
rectly connected.
Set the parameter  e   if
not used or to disable.
Jumper contact FT1 with contact
COM, if not used or to disable. Check
connection referring to relative con-
nection diagram
 
Photocell FT2 not connected or incor-
rectly connected.
Set the parameter  e   if
not used or to disable.
Jumper contact FT2 with contact
COM, if not used or to disable. Check
connection referring to relative con-
nection diagram
 )(
At least 3 limit switches in open con-
tact state or not connected.
-
Check connection of limit switches.
 )$
Both gate leaves at open limit
switch.
-
-
Open limit switch not connected.
-
Check connection of limit switches.
 )&
Both gate leaves at closed limit
switch.
-
-
Closed limit switch not connected. - Check connection of limit switches.
 )
LEAF 1 limit switches not connected
or incorrectly connected.
-
Check connection of limit switches.
 )
LEAF 2 limit switches not connected
or incorrectly connected.
-
Check connection of limit switches.
 
LEAF 1 open limit switch not con-
nected or incorrectly connected.
Or LEAF 1 is open.
-
Check connection of limit switches.
 
LEAF 1 closed limit switch not con-
nected or incorrectly connected.
Or LEAF 1 is closed.
-
Check connection of limit switches.
 
LEAF 2 open limit switch not con-
nected or incorrectly connected.
Or LEAF 2 is open.
-
Check connection of limit switches.
 
LEAF 2 closed limit switch not con-
nected.
Or LEAF 2 is closed.
-
Check connection of limit switches.
SS 
If occurs with no voluntary command,
the contact (N.O.) may be faulty or
one of the buttons may be incorrectly
connected.
-
Check PP - COM contacts and con-
nections to buttons.
&+ 
-
Check CH - COM contacts and con-
nections to buttons.
DS 
-
Check AP - COM contacts and con-
nections to buttons.
SH 
-
Check PED - COM contacts and con-
nections to buttons.
2U
If occurs with no voluntary command,
the contact (N.O.) may be faulty or the
timer may be incorrectly connected.
-
Check ORO - COM contacts. Contact
must not be jumpered if not used.
N.B. Press TEST button to exit from the TEST Mode.