Platinum Plus
19
Standard Mode Programming Steps
Install | Scale
You can program scale options in the
Management Menu, and calibrate
scales in the Service Menu.
cost feed inventory
method.
2. Feed Bin scales require a
key in the optional scale
card.
3. Duplicated bird scales (two
scale-1) combine for a
single data base.
6.7
Install |
Temperature
Definition
Select the temperature sensors to use
for each function using the +/- key to
apply and remove check marks.
Normally do not assign sensors
to the fans. The sensors
defined for the house operation
mode apply to any device with
no specifically assigned
sensors.
6.8
Install |
Fan Air
Capacity
Enter the fan air capacity for each of
your exhaust and tunnel fans. Under
Help | Set enter the house dimensions
so the Platinum Plus can calculate
wind chill temperature corrections.
If you group fans using the
same as # relay codes, count
the group as a single fan.
6.9
Install |
System
Parameters
You can access system parameters as
‘Set’ parameters under Help in each
menu. Press the Help key, then choose
the Set option. For experienced users,
all system parameters are available
under this menu.
Some parameters may not
appear under Help | Set if they
do not apply. For example,
they may not apply if there is
no such equipment installed.
Step 2 … 1. Control Menu Comments:
1.1
Control |
Temp &
Timer Settings
1. Set On and Off Temperatures for
all temperature related devices.
2. Assign the Minimum Ventilation
timer to the min vent fans.
3. Assign 1 of the 4 auxiliary timers
to devices if desired.
4. Under Help | Set:
a) Set the Minimum number of
Tunnel Fans On.
b) Set the Tunnel Exit Delay
c) Set Non Brood area temperature
relative to target temperature.
d) Set Stir Fan Delay from the end
of the Min Vent Timer and
Operation Duration.
e) Choose if Stir fans continue to
1. Program the minimum
ventilation timer and the
auxiliary timers in their
own menus.
2. The minimum on/off
temperature difference is
0.5ºF.
3. If temperature curve is ON
in Control, Control Mode,
you cannot adjust the set
temperature.
4. Tunnel ON and OFF
temperatures should be at
least 3.0ºF apart.
5. To prevent yo-yoing, do
not increase ventilation at
the tunnel ON temperature.