Poultry House Control
22
Standard Mode Programming Steps
can be active.
3. From Temp: temperature above
which extra system can be active.
4. To Temp: temperature below
which extra system can be active.
5. From Humidity: humidity above
which extra system can be active.
6. To Humidity: humidity below
which extra system can be active.
7. On Time (seconds): cycle time, on
setting.
8. Off Time (seconds): cycle time,
off setting.
Temp for operation.
3. Choose temperature
sensors for extra systems in
Install, Temperature
Definition Menu. Assign a
relay in Install | Relay
Layout.
1.9
Control |
Pressure
1. Enter low and high pressure limits
for both minimum ventilation and
tunnel ventilation.
2. Enter low and high pressure alarm
settings.
3. Check the Help | Set parameters:
a) Wind Gust Delay
b) Pressure During Tunnel
c) Transitional Tunnel
d) Min Vent Using Inlet or Tunnel
e) Emergency Pressure Delay
f) Curtain Position in Emergency
g) Minimum Tunnel Curtain Level
h) Minimum Tunnel Level to Start
Fans
i) Vent Motor Slow/Fast
j) Time to Produce Pressure
1. Transitional Tunnel
permits controller to open
tunnel curtain in cross
ventilation if the side vent
doors are already 100%
open and pressure is too
high.
2. Emergency Pressure is
response to high pressure
alarm situations, which can
occur when a tunnel curtain
fails to open, for example.
By default, all air sources
open. Restore normal
operation using
Management | Alarm
Reset.
3. Min Tun Curt Level sets
actual level if you choose
no pressure in tunnel.
1.10
Control |
Control Mode
Choose house operating modes,
whether to allow tunnel and turn
curves on or off.
To temporarily adjust set
temperatures for mildly ill
birds (after vaccination), adjust
the offset at the hotkey.
Review Standard Mode Example next,
then Continue with Shared Menus on Page 57