EasyManua.ls Logo

Samwon Tech TEMP880S - Auto Tuning Function and Cautions

Default Icon
104 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SAMWONTECH
1st Edition of TEMP880S IM : Sep. 21. 2005 Page 32 / 101
Auto tuning is a function for automatically adjusting P, I, D parameter to the optimal condition
suitable for a system for controlling a heat shock tester.
Auto tuning can be performed only when thermal shock tester is running, and be done for a
aboratory currently operated. For example, when auto tuning is operated during the operation
of the present high temperature room. When auto tuning is completed, P, I, D values
automatically calculated by auto tuning are automatically set in P, I, D parameter of high
temperature part of laboratory and of high temperature room.
Diagram 2-22. Example of Auto Tuning Operation
It is impossible to perform auto tuning or auto tuning is forced to be terminated under the
following conditions.
When a thermal shock tester stops running
When a sensor burns out
When a user manually stops auto tuning before the automatic termination after the
operation of auto tuning
A manufacturing company sets P, I, D parameters so that a thermal shock tester can make
optimal control through experiment during the production of the tester. When performing auto
tuning, P, I, D parameters related to control initially set up are changed. Therefore, controlling
features of a thermal shock tester can be changed. Accordingly, when you intend to operate
auto tuning, please discuss it with a heat shock tetster manufacturing company without fail.
AUTO TUNING
Caution for Auto Tuning
AT start
AT end
AT start
AT end
A
T in hi
g
h
A
T in low

Related product manuals