1st Edition of TEMP880S IM : Sep. 21. 2005 Page 95 / 101
4.4.4.2 Reading a Program Pattern
The following order should be performed to read the program pattern which is set up at TEMP880S.
1 Set up the Pattern No. of Program at D1000
2 Set up the READ TRIGGER (‘2’) at D1003
3 Wait until it’s DONE(‘1’) after reading the data of D1004
4 Read data recorded at D1010~D1032.
4.4.4.3 Writing the Program Pattern
The following order should be done to write program pattern at TEMP880S.
1 Set up the program pattern at D1000
2 Set up data to record at D1010~D1031
3 Set up the WRITE TRIGGER ('3') at D1003
4 Wait until it’s DONE (‘1) after reading the data of D1004
4.4.4.4 Copy/Delete of Pattern & Insert/Delete of Segment
Copy of Program Pattern
1 Set up the original pattern No. to copy at D1000
2 Set up the No. of pattern at D1001 to copy the original pattern
3 Set up D1003 PT COPY TRIGGER('4') at D1003
4 Wait until it’s DONE (‘1) after reading the data of D1004
Delete of Program Pattern
1 Set up the No. of pattern, which will be deleted, atD1000
2 Set up PT DEL TRIGGER('5') at D1003
3 Wait until I’t s DONE (‘1) after reading the data of D1004