Appendix B Programmable Parameters 131
Table B-4a Analog Output Groups
Code Description
nonE Analog output channel disabled
rt.Ph Real-time per phase measurements
rt.to Real-time three-phase total measurements
rt.Au Real-time auxiliary measurements
Ar.Ph Average per phase measurements
Ar.to Average three-phase total values
Ar.Au Average auxiliary measurements
dnd Present demands
hr.U1 L1/L12 phase harmonic voltages (odd harmonics)
hr.U2 L2/L23 phase harmonic voltages (odd harmonics)
hr.U3 L3 phase harmonic voltages (odd harmonics)
hr.C1 L1 phase harmonic currents (odd harmonics)
hr.C2 L2 phase harmonic currents (odd harmonics)
hr.C3 L3 phase harmonic currents (odd harmonics)
hr.Ac Harmonic total active powers (odd harmonics)
hr.rE Harmonic total reactive powers (odd harmonics)
hr.PF Harmonic total power factors (odd harmonics)
Table B-4b Analog Output Parameters
Parameter Unit Range/scale À
Group Code Name
Á
Zero Full
nonE nonE Output channel disabled n/a 0 0
rt.Ph
Real-time values per phase
U 1 Voltage L1/L12 V 0 Vmax
U 2 Voltage L2/L23 V 0 Vmax
U 3 Voltage L3/L31 V 0 Vmax
cur1 Current L1 A 0 Imax
cur2 Current L2 A 0 Imax
cur3 Current L3 A 0 Imax
Ac.P1 kW L1 kW -Pmax Pmax
Ac.P2 kW L2 kW -Pmax Pmax
Ac.P3 kW L3 kW -Pmax Pmax