132
Appendix B Programmable Parameters
Table B-4b Analog Output Parameters
Parameter Unit Range/scale À
Group Code Name
Á
Zero Full
rE.P1 kvar L1 kvar -Pmax Pmax
rE.P2 kvar L2 kvar -Pmax Pmax
rE.P3 kvar L3 kvar -Pmax Pmax
AP.P1 kVA L1 kVA 0 Pmax
AP.P2 kVA L2 kVA 0 Pmax
AP.P3 kVA L3 kVA 0 Pmax
PF1 Power factor L1 n/a -1.00 1.00
PF2 Power factor L2 n/a -1.00 1.00
PF3 Power factor L3 n/a -1.00 1.00
th.U1 Voltage THD L1/L12 % 0 100.0
th.U2 Voltage THD L2/L23 % 0 100.0
th.U3 Voltage THD L3 % 0 100.0
th.C1 Current THD L1 % 0 100.0
th.C2 Current THD L2 % 0 100.0
th.C3 Current THD L3 % 0 100.0
HFc.1 K-Factor L1 n/a 1.0 999.9
HFc.2 K-Factor L2 n/a 1.0 999.9
HFc.3 K-Factor L3 n/a 1.0 999.9
rt.to
Real-time total values
Ac.P Total kW kW -Pmax Pmax
rE.P Total kvar kvar -Pmax Pmax
AP.P Total kVA kVA 0 Pmax
PF Total PF n/a -1.00 1.00
PF.LG Total PF Lag n/a 0 1.00
PF.Ld Total PF Lead n/a 0 1.00
rt.Au
Real-time auxiliary measurements
Au.C Auxiliary current mA/A 0 Iaux max
nEU.C Neutral current A 0 Imax
FrEq Frequency  Hz 0 100.0
U.Unb Voltage unbalance % 0 300
C.Unb Current unbalance % 0 300
Ar.Ph
Average values per phase
U 1 Voltage L1/L12 V 0 Vmax