Appendix B Programmable Parameters 135
Table B-4b Analog Output Parameters
Parameter Unit Range/scale À
Group Code Name
Á
Zero Full
H01-H39 Harmonic H01-H39 V 0 Vmax
hr.U2
L2/L23 phase harmonic voltages (odd harmonics)
H01-H39 Harmonic H01-H39 V 0 Vmax
hr.U3
L3 phase harmonic voltages (odd harmonics)
H01-H39 Harmonic H01-H39 V 0 Vmax
hr.C1
L1 phase harmonic currents (odd harmonics)
H01-H39 Harmonic H01-H39 A 0 Imax
hr.C2
L2 phase harmonic currents (odd harmonics)
H01-H39 Harmonic H01-H39 A 0 Imax
hr.C3
L3 phase harmonic currents (odd harmonics)
H01-H39 Harmonic H01-H39 A 0 Imax
hr.Ac
Harmonic total active powers (odd harmonics)
H01-H39 Harmonic H01-H39 kW -Pmax Pmax
hr.rE
Harmonic total reactive powers (odd harmonics)
H01-H39 Harmonic H01-H39 kvar -Pmax Pmax
hr.PF
Harmonic total power factors (odd harmonics)
H01-H39 Harmonic H01-H39 n/a -1.00 1.00
À The parameter window resolution is 7 digits. The parameter limits are as follows:
Vmax (660V input option) = 660 [V] @ PT ratio = 1.0 and Vmax = 144 × PT
ratio [V] @ PT ratio > 1.0
Vmax (120V input option) = 144 × PT Ratio [V]
Imax = 1.2 × CT primary current [A]
Iaux max = 1.2 × Auxiliary CT primary current [mA/A]
Pmax = (Imax × Vmax × 3)/1000 [kW] @ Wiring mode 4Ln3 or 3Ln3
Pmax = (Imax × Vmax × 2)/1000 [kW] @ Wiring mode 4LL3, 3OP2, 3dir, 3OP3
or 3LL3
Á Readings with a decimal point are displayed as MW, Mvar, MVA.
 The actual frequency range is 45.0 - 65.0 Hz