7 General Description of Functions
EN-US · 30.30.00.00424 · 07 · 10/23 39 / 86
7.16.2Device Access Locks
In IO-Link mode, the “Device access locks” default parameter is available to prevent changes to parameter
values using the user menu or IO-Link. You can also prevent the use of the Data storage mechanism de-
scribed in IO-Link Standard V1.1.
Bit Meaning
0 Parameter write access locked
(Parameters cannot be changed via IO-Link)
1 Data storage locked
(Data storage mechanism is not triggered)
2 Local parametrization locked
(Parameters cannot be changed via the user menu)
Coding for the device access locks
A menu lock using the Device access locks parameter has a higher priority than the menu PIN. In other
words, this lock cannot be bypassed by entering a PIN and remains in SIO mode.
It can only be canceled using IO-Link, not on the device itself.
7.17Resetting to Factory Settings
This function restores the ejector configuration of the initial setup and the settings of the active produc-
tion setup profile to the factory settings.
WARNING
By activating/deactivating the product, output signals lead to an action in the pro-
duction process!
Personal injury
4 Avoid possible danger zone.
4 Remain vigilant.
The function is executed using the rE5 menu item in the configuration menu or via IO-Link:
1. Press the MENU button for more than 3 seconds.
ð When the menu is locked, enter the valid PIN.
2. Use the UP or DOWN button to select the menu item rE5.
3. Confirm using the MENU button.
ð YE5 appears on the display.
4. Press the MENU button for more than 3 seconds.
ð The ejector is reset to the factory settings.
ð The display flashes for a number of seconds and then returns to display mode.
The function for resetting factory settings does not affect the following elements:
The counter readings
The zero-point adjustment of the sensor
The IO-Link parameter “Application Specific Tag”
The production setup profiles, which are currently deactivated
The factory settings for the ejector are listed in the Technical Data section.