EasyManua.ls Logo

Schwank Control Touch - Page 42

Schwank Control Touch
71 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Revision: 3.0 Page 41 of 70
Assigning MODBUS addresses
It is essential that each IC 4000 automatic burner control unit
[for MODBUS communication with the SchwankControl central control],
is assigned a unique MODBUS address.
The MODBUS address is set via DIP switch
in the lower right corner of the board.
A maximum of 32 addresses can be assigned per zone.
All IC 4000s are delivered with the MODBUS address 1.
Figure 41: [MODBUS addressing]
IC 4000 delivery status
The automatic burner control unit is parameterised for MODBUS communication in the as-
delivered state.
When used in systems with relay control, the parameterisation must be adapted accordingly
[see separate operating manual of the Schwank heaters used].
Please note that the wiring of the GDM plug must also be changed when used in systems with
relay control.

Table of Contents