Revision: 3.0 Page 64 of 70
RTS offset: 0°C
Preheating time: Off
Heating gradient: 0.10min/K²
KP: 20
Tn: 120 sec
Tv: 0 sec
Minimum running time: 120s [2min]
Minimum pause time: 60s [1min]
Minimum full load: 60s [1min]
Fan lag time: 180s [3min]
Minimum running time: 600s [10min]
Minimum pause time: 60s [1min]
Minimum full load time: 60sec [1 min]
Fan lag time: 900sec [15min]
Minimum runtime: 300sec [5min]
Minimum pause time: 60sec [1min]
Minimum full load time: 60sec [1min]
Fan lag time: 0sec [0min]
Switch-off threshold: 5%
Switch-on threshold: 20%
Switch-off threshold: 5%
Switch-on threshold: 20%
Full load threshold Off:50%
Full load threshold On: 60%
Switch-off threshold: 5%
Switch-on threshold: 20%
Modulation start value: 90%