Revision: 3.0 Page 64 of 70
Parameter [Expert]
Zone1 - Zone4:
RTS offset: 0°C
Preheating time: Off
Heating gradient: 0.10min/K²
KP: 20
Tn: 120 sec
Tv: 0 sec
Luminous heater:
Minimum running time: 120s [2min]
Minimum pause time: 60s [1min]
Minimum full load: 60s [1min]
Fan lag time: 180s [3min]
Tube heater:
Minimum running time: 600s [10min]
Minimum pause time: 60s [1min]
Minimum full load time: 60sec [1 min]
Fan lag time: 900sec [15min]
Warm air heater:
Minimum runtime: 300sec [5min]
Minimum pause time: 60sec [1min]
Minimum full load time: 60sec [1min]
Fan lag time: 0sec [0min]
Single-stage
Switch-off threshold: 5%
Switch-on threshold: 20%
Two-stage
Switch-off threshold: 5%
Switch-on threshold: 20%
Full load threshold Off:50%
Full load threshold On: 60%
Modulating
Switch-off threshold: 5%
Switch-on threshold: 20%
Modulation start value: 90%
12.4. QR Code
The QR code on the type plate and in the info screen of the connected control opens the
SchwankControl product information within the Schwank website.
As soon as the SchwankControl is connected to a computer or the local network with a LAN cable
[connection only available on control unit] and an IP is displayed in the info screen, the QR code that
starts the webapp within a browser window during scanning changes, see section 13.5