3-6 Communications Date Code 20011026
SEL-321/321-1 Instruction Manual
Changing Access Levels
To enter Level 1, type the following on a terminal connected to the relay via a serial port:
=ACCESS <ENTER>
ACCESS <ENTER>ACCESS <ENTER>
ACCESS <ENTER>
The response is:
Password: ? @@@@@@
Enter the Level 1 password: OTTER and press <ENTER>. The response is:
EXAMPLE: BUS B, BREAKER 3 Date: 02/01/93 Time: 15:10:49.966
Level 1
=>
At the "=>" prompt you can execute any Level 1 command. Commands at this level involve
display of information and generation of reports. No relay settings can be changed from Access
Level 1. Change to other access levels in a similar manner using the commands and passwords
shown in Figure 3.1.
Command Format
Commands consist of three or more characters; only the first three characters of any command are
required. You may use upper or lower case characters without distinction, except in passwords.
You must separate arguments from the command by spaces, commas, semicolons, colons, or
slashes. Enter commands after the terminal displays the access level prompt.
DESCRIPTION OF COMMANDS
2ACCESS
Use the 2ACCESS command to enter Access Level 2. A password is required. The default
password at this level is set to TAIL at the factory. Use the PASSWORD command at Level 2 to
change passwords.
The following display indicates successful access:
=>2ACCESS <ENTER>
2ACCESS <ENTER>2ACCESS <ENTER>
2ACCESS <ENTER>
Password: ? TAIL <ENTER>
TAIL <ENTER>TAIL <ENTER>
TAIL <ENTER>
EXAMPLE: BUS B, BREAKER 3 Date: 02/01/93 Time: 15:10:58.903
Level 2
=>>