EasyManua.ls Logo

Schweitzer Engineering Laboratories SEL-321 - Zone 3 Setting

Schweitzer Engineering Laboratories SEL-321
396 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Date Code 20011026 Applications 5-5
SEL-321/321-1 Instruction Manual
Zone 2 element settings with a reach of 120% of protected line impedance account for the effects
of infeed. This point must be verified using a fault study to calculate the apparent ohms at the
local terminal for a fault at the remote end of the transmission line. In the example system, 120%
is selected for the Zone 2 elements with assurance that all faults in line 2 are detectable, even
with infeed from the remote terminals.
Assuming the Zone 1 reach for the line protection at Breakers 5 and 11 is set for 80% of the line
impedances of Lines 3 and 6 respectively, verify that a Zone 2 reach of 120% for Breaker 3 does
not overreach the Zone 1 elements at Breakers 5 and 11.
Line 2 Impedance + [0.8 Line 3 Impedance] = 78.03 + [0.8 • 39.12 ]
= 109.33 primary
When Zone 2 at Breaker 3 has a set reach of 120%, the effective reach is:
Zone 2 at Bkr. 3 = 1.20 78.03 = 93.64 primary 84°
Since 93.64 < 109.33 , the Zone 2 setting of 120% at Breaker 3 does not overreach the
Zone 1 protection of Lines 3 and 6. Any effect of infeed tends to increase the apparent ohms
seen at Breaker 3 for faults on Lines 3 and 6.
The Zone 2 quadrilateral element setting is based upon the same requirement established for the
Zone 2 mho elements. The reactive reach is set the same as the mho distance setting. The
resistive reach determines sensitivity for high resistance faults on a radial basis. For this
example, the Zone 2 resistive reach is set for 50 primary.
Zone 3 Setting
This example uses a Permissive Overreaching Transfer Trip (POTT) communications scheme.
The current reversal block, echo and weak-infeed logic require reversal of the Zone 3 elements.
The Zone 3 element reach at Breaker 3 must be selected to detect all out-of-section faults also
detected by the overreaching elements at Breaker 4. At a minimum, the Zone 3 reach setting
must equal the impedance the overreaching element at Breaker 4 sees beyond Breaker 3.
Assuming the Zone 2 reach for the line protection at Breaker 4 is set for 120% of the line
impedance of Line 2, the Zone 3 reach at Breaker 3 is set at 120% of the Zone 2 overreach from
Breaker 4.
When Zone 2 at Breaker 4 has a set reach of 120%, the effective reach is:
Zone 2 at Bkr. 4 = 1.20 78.03 = 93.64 84°
The Breaker 4 overreach is equal to the Zone 2 setting minus the line impedance:
93.64 - 78.03 = 15.61 primary
Zone 3 Reach = 1.2 15.61 primary 84° = 18.73 primary 84°

Table of Contents

Related product manuals