Introduction
Configurable Signal Silence Inhibit and Auto Signal Silence Timers. For UL installations,
disable the Auto Signal Silence Timer.
Subsequent Alarm, Supervisory, and Trouble operation.
Four wire reset-able smoke power supply.
Relay Contacts for Common Alarm, Common Supervisory, Common Trouble, and
Auxiliary Alarm Relay (disconnectable).
RS-485 Interface for MR-2300 Series Remote Multiplex Annunciators and Smart relay
Module.
Optional Modules for additional Relay Circuits, City Tie and Polarity Reversal Signaling.
Extensive transient protection.
Easy configuration of the panel using LCD service tool (CFG-300).
Releasing circuit protection from false alarm by disconnecting the battery if the voltage
falls below 20.4V at the last releasing device.