Electrical values 0 V ≤ V
out
1)
≤ V
S
(V
S
−1.5 V) ≤ V
out
≤ V
S
at I
out
2)
≤ 100 mA
1)
Output voltage.
2)
Output current.
NOTE
Assign the functions for the digital outputs in the device using a configuration tool, e.g.,
the configuration software SOPAS ET.
14.7.9 Wiring the external digital outputs of the device in the CDM420-0006
Device = CLV61x-xx0xxx (serial variant)
Load (e.g. PLC) 4
GND
For inductive load: 6
V
out
Device 1
Aux
(RS-232)
CDM420-0006
CMC600 3
+24 V* (V
S
)
CAux Out B
36
GND
6
Shield
“External
output A” 2
5
Figure 72: Wiring “Aux Out 1” and “Aux Out 2” external digital outputs of the device in the connection module CDM420-0006.
1
Device
2
Logical “External output” in the device
3
The optional CMC600 parameter cloning module is required in the connection module in order to use the additional
external digital inputs and outputs of the device.
4
Load (e.g. PLC)
5
Output voltage V
out
6
With inductive load: see note
Inductive load
NOTE
Provide an arc-suppression switch at the digital output if inductive load is present.
b
Attach a freewheeling diode directly to the load for this purpose.
Table 54: Assignment of placeholders to the external digital outputs
Device CDM420-0006
External output A Signal B Terminal C
1 Aux Out 1 40
14 ANNEX
110
O P E R A T I N G I N S T R U C T I O N S | CLV61x 8017840/19OF/2021-10-28 | SICK
Subject to change without notice