Measures for small system installations
For smaller installations with only slight potential differences, insulated mounting of the
device and peripheral devices may be an adequate solution.
U
System
Controller
Power Supply
SICK
Device
8 6
5
21 3
4
7
= 9
= ß
Figure 18: Example: Prevention of equipotential bonding currents in the system configuration by
the insulated mounting of the device
1
System controller
2
Device
3
Voltage supply
4
Grounding point 3
5
Insulated mounting
6
Grounding point 2
7
Ground potential difference
8
Grounding point 1
9
Metal housing
ß
Shielded electrical cable
Even in the event of large differences in the ground potential, ground loops are effec‐
tively prevented. As a result, equalizing currents can no longer flow via the cable shields
and metal housing.
NOTICE
The voltage supply for the device and the connected peripheral devices must also
guarantee the required level of insulation.
Under certain circumstances, a tangible potential can develop between the insulated
metal housings and the local ground potential.
6.2 Wiring instructions
NOTE
Pre-assembled cables can be found online at:
www.sick.com/CLV61x
6 ELECTRICAL INSTALLATION
36
O P E R A T I N G I N S T R U C T I O N S | CLV61x 8017840/19OF/2021-10-28 | SICK
Subject to change without notice

Table of Contents

Other manuals for SICK CLV61 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SICK CLV61 Series and is the answer not in the manual?

SICK CLV61 Series Specifications

General IconGeneral
BrandSICK
ModelCLV61 Series
CategoryBarcode Reader
LanguageEnglish

Related product manuals