Short-circuit protected and temperature protected
Not electrically isolated from the supply voltage V
S
Electrical values 0 V ≤ V
out
1)
≤ V
S
(V
S
−1.5 V) ≤ V
out
≤ V
S
at I
out
2)
≤ 100 mA
1)
Output voltage
2)
Output current
NOTE
Assign the functions for the digital outputs in the device using a configuration tool, e.g.,
the configuration software SOPAS ET.
14.6.9 Wiring the external digital outputs of the device in the CDM420-0001
Device = CLV61x-xx0xxx (serial variant)
Load (e.g. PLC) 4
GND
For inductive load: 6
V
out
Device 1
Aux
(RS-232)
CDM420-0001
CMC600 3
+24 V* (V
S
)
CAux Out B
36
GND
6
Shield
“External
output A2
5
Figure 61: Wiring external digital outputs “Aux Out 1” and “Aux Out 2” of the device in the connection module CDM420-0001.
1
Device
2
Logical “External output” in the device
3
The optional CMC600 parameter cloning module is required in the connection module in order to use the additional
external digital inputs and outputs of the device.
4
Load (e.g. PLC)
5
Output voltage V
out
6
With inductive load: see note
Inductive load
NOTE
Provide an arc-suppression switch at the digital output if inductive load is present.
b
Attach a freewheeling diode directly to the load for this purpose.
14 ANNEX
98
O P E R A T I N G I N S T R U C T I O N S | CLV61x 8017840/19OF/2021-10-28 | SICK
Subject to change without notice

Table of Contents

Other manuals for SICK CLV61 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SICK CLV61 Series and is the answer not in the manual?

SICK CLV61 Series Specifications

General IconGeneral
BrandSICK
ModelCLV61 Series
CategoryBarcode Reader
LanguageEnglish

Related product manuals