Description
18/121 Revision 05 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DJH • 500-8067.9
Cable plugs for single cable connection (interface type C)
Cable type Cable plug
Make Ser.
no.
Type Design
T/W
1, 2
Conductor
cross-
section
[mm
2
]
Design
2
Thermoplastic-insulated cables ≤ 12 kV according to IEC / EN 60502-2 / VDE 0276-620
1- or 3-core cable,
PE and XLPE-insulated
N2YSY (Cu) and N2XSY (Cu)
or
NA2YSY (Al) and NA2XSY (Al)"
Nexans 1 400TB/G, 430TB/G, 480TB/G T 35...300 Screened
2 400LB/G W 35...300 Screened
3 484TB/G T 70...630 Screened
4 440TB/G T 185...630 Screened
nkt cables 5 CB 24-630 T 25...300 Screened
6 AB 24-630 T 25...300 Insulated
7 CB 36-630 (1250) T 300...630 Screened
Südkabel 8 SET 12 T 50...300 Screened
9 SEHDT 13 T 185...500 Screened
Prysmian Kabel und Systeme
(Pirelli Elektrik)
10 FMCTs-400 T 25...300 Screened
3M Germany 11 93-EE 705-6 / -95 T 50...95 Screened
12 93-EE 705-6 / -240 T 95...240 Screened
TE Connectivity 13
RICS 51 ... with IXSU
3
T 25...300 Insulated
14
RICS 31 ... with IXSU
3
T 25...300 Insulated
15 RSTI-39xx T 400...800 Screened
Thermoplastic-insulated cables 15 / 17.5 / 24 kV according to IEC / EN 60502-2 / VDE 0276-620
1- or 3-core cable,
PE and XLPE-insulated
N2YSY (Cu) and N2XSY (Cu)
or
NA2YSY (Al) and NA2XSY (Al)
Nexans 16 K400TB/G, 430TB/G, 480TB/
G
T 35...300 Screened
17 K400LB/G W 35...300 Screened
18 484TB/G T 70...630 Screened
19 K440TB/G T 185...630 Screened
nkt cables 20 CB 24-630 T 25...300 Screened
21 AB 24-630 T 25...300 Insulated
22 CB 36-630 (1250) T 300...630 Screened
Südkabel 23 SET 24 T 50...240 Screened
24 SEHDT 23.1 T 300 Screened
25 SEHDT 23 T 185...630 Screened
Prysmian Kabel und Systeme
(Pirelli Elektrik)
26 FMCTs-400 T 25...240 Screened
3M Germany 27 93-EE 705-6 / -95 T 25...95 Screened
28 93-EE 705-6 / -240 T 95...240 Screened
TE
Connectivity
for 1-core
cables
29
RICS 51 ... with IXSU
3
T 25...300 Insulated
30 RSTI-58xx T 25...300 Screened
31 RSTI-59xx T 400...800 Screened
for 3-core
cables
32
RICS 51 ... with IXSU
3
T 25...300 Insulated
33 RSTI-58xx + RSTI-TRFxx T 25...300 Screened
Paper-insulated mass-impregnated cables ≤ 12 kV according to IEC / EN 60055-2 / VDE 0276-621
3-core cable, paper-insulated
N(A)KLEY, N(A)KBA, N(A)KBY
TE Connectivity 34 RICS 51... with UHGK / EPKT T 95...300 Insulated
3-core cable, paper-insulated
N(A)EKBA, N(A)KLEY
35
RICS 51... with IDST 51
3
T 50...300 Insulated
Paper-insulated mass-impregnated cables 15 / 17.5 / 24 kV according to IEC / EN 60055-2 / VDE 0276-621
1-core or 3-core cable, paper-
insulated
N(A)EKBA, N(A)KLEY
TE Connectivity 36
RICS 51 ... with IDST 51
3
T 35...240 Insulated
1
T = Cable T-plug, W= Cable elbow plug
2
Use of current transformers and current sensors in combination with insulated systems on request
3
Discontinued by the manufacturer