7BSpecifications
54BTechnical data FDOOT221, FDOOT241-x / -Ax
8
123 |
138
Building Technologies
007004_t_en_--
Fire Safety
2015-11-04
Collective maximum current connection factor/alarm verification
(FDOOT241-9)
The default parameter set (parameter set 0) is set in all fire detectors when
delivered.
Use as
Parameter set
Maximum
current
connection
factor for
ES < 30
Maximum
current
connection
factor for
ES 30
1
Alarm verification
on control panel
permitted with
detector ES < 13
(verification time at
the control panel
≥50 s)
Alarm verification on control
panel permitted with detector
ES 13 (verification time at the
control panel ≥ 30 s)
No.
Designation
Neural fire
detector
(FDOOT)
2 Robust
2
1.5
No
Yes
4 Balanced
5 Suppression
6 Fast Response 2 1.5 Yes Yes
7 High Compensation 2 1.5
2
No Yes
0 (ES ≥13) High Compensation 1.25
2
Yes
0 (ES <13) Insensitive 1.5 No
8 High Suppression 1.5 Yes
9 High Sensitive Fast 1.5 Yes
Wide-
spectrum
smoke
detector
(FDO)
0 Universal 2 1.5 No Yes
1 Universal
2 Robust
3 Sensitive 2 1.5 Yes Yes
Heat detector
(FDT)
0…4 All parameter sets 2 1.5 No Yes
1
For CS1115, the maximum current connection factor values in the column apply for ES <30.
2
Different connection factors due to the different measuring cycles.