Collective maximum current connection factor/alarm verification
(FDOOT241-A9)
The default parameter set (parameter set 0) is set in all fire detectors when
delivered.
Use as
Parameter set no.
Parameter set name
Maximum
current
connection
factor
1
Alarm verification permitted on
control panel
Neural fire detector (FDOOT) 0 High Compensation
1
2
Yes
2 Robust
1.25 Yes
4 Balanced
1.25 Yes
5 Suppression
1.25 Yes
6 Fast Response
1.25 Yes
7 High Compensation
1
2
Yes
8 High Suppression
1.25 Yes
9 High Sensitive Fast
1.25 Yes
11 Super Sensitive
1.25 Yes
Wide-spectrum smoke detector
(FDO)
0 Universal
1.25 Yes
1 Universal
1.25 Yes
2 Robust
1.25 Yes
3 Sensitive
1.25 Yes
5 Super Sensitive
1.25 Yes
6 Ultra Sensitive
1.25 Yes
Heat detector (FDT) 0…4 All parameter sets
1.25 Yes
1
The maximum current connection factor of 1.5 applies to CS1115.
2
The maximum current connection factor of 1.25 applies to SIGMASYS SMG-S and SPF3500.