7BSpecifications
54BTechnical data FDOOT221, FDOOT241-x / -Ax
8
125 |
138
Building Technologies
007004_t_en_--
Fire Safety
2015-11-04
MS8/PMT detector line (FDOOT241-8)
Detector line
Operating voltage (modulated) DC 14…28 V
Operating current (quiescent) 200 μA
Maximum current connection factor 2
Protocol MS8/PMT
Compatibility See 'List of compatibility'
External alarm indicators
External alarm indicators which can be
connected
With ES <30 0 (not supported)
With ES ≥30 Max. 2
Voltage Typ. DC 6…17 V
Current 9…15 mA
Length of line Max. 30 m with unshielded cables,
or when the shielding is connected
to the positive pole of the detector
base
Max. 5 m, if the shielding is
connected to earth
Flashing interval times:
Bright 15 ms
Dark 1 s

Table of Contents