Configuring and commissioning using ETS
8.4 General parameter assignments
CMK2000
42 Operating Instructions, 11/2015, A5E34877550B/001
Note
Guideline for setting the update rate
If the cycle time of the LOGO! is overloaded due to a high level of data exchange (high
update rate), a larger value must be used for the update rate, e.g. 200 ms.
If the response time for LOGO
KNX is too slow, e.g. for switching lights, a smaller value
must be selected for the update rate, e.g. 50 ms.
The update rate can be set as follows:
50 ms
100 ms
150 ms (default)
200 ms
300 ms
Own IP address and subnet mask
In these fields you enter the IP address and subnet mask of the CMK2000.
Example of private Class C network:
LOGO!
CMK2000
IP address 192.168.0.1 192.168.0.10
Subnet mask
255.255.255.0
Password for web interface
It is necessary to enter a password to access the CMK2000 from a PC (using web browser).
You define the password here.
The default password is "Admin"
NOTICE
Immediately change the default password to a new one.
Protect access to the web server by using a "strong" password. "Strong" passwords are
at least eight characters long, consist of letters, numbers and special characters, are not
words which can be found in a dictionary, and are not names or identifiers which can be
derived from personal data. Keep the password secret and change it frequently.