18 DKFD.PS.027.W3.02
2. Technical data
Technical data
SITRANS F M MAGFLO
Coil cable Electrode cable
Basic data No. of conductors 2 3
Min. sqr. area 0.5 mm
2
0.2 mm
2
Screen Yes Yes
Max. capacitance N.A. 350 pF/m
Max. cable loop Media temperature: < 100°C 40 Ω N.A.
resistance < 200°C6 Ω N.A.
2.8.1
Sensor cables and
conductivity of medium
Conductivity of Compact installation:
medium Liquids with an electrical conductivity ≥ 5 µS/cm.
For a conductivity between 5 and 10 µS/cm, the repeatability may degrade to
±0.5% of actual flow.
Remote
installation:
Standard cable
Note
For detection of empty sensor the min. conductivity must always be
≥ 20 µS/cm and the max. length
of electrode cable when remote mounted is 50 metres. Special cable must be used.
For remote mounting in Ex applications special cable cannot be used, empty sensor cannot be
detected and the electrically conductivity must be
≥ 30 µS/cm.
For remote mounted CT installations the max. cable length is 200 metres.
2.8.2
Minimum accept data for
cable
2.9
HART
communication
add-on module
Application MAG 6000, MAG 6000 CT
Optional available as factory mounted in MAG 5000
Communication standard Bell 202 frequency shift keying (f.s.k.) standard
Communication modes • Single loop mode
• Multi-drop mode, 15 slave devices
Communicator Rosemount Hand-held communicator type 275
Cable specification
Communication mode /
Single loop
Q [mm
2
] CU ≥ 0.2 mm
2
/AWG 24
Screen Yes (Overall screen)
Loop resistance
Min.
230 Ω
Max.
800 Ω
Cable capacity ≤ 400 pF/m
Cable length 1500 m
Twisted pair Yes
HART
is a registered trademark of the HART Communication Foundation.
2.10
Cable data
(Supplied by Siemens
Flow Instruments)
Standard cable Special cable
(electrode/coil) (electrode)
Basic data No. of conductors 3 3
Sqr. area 1.5 mm
2
0.25 mm
2
Screen Yes Double
Color code Brown, blue, black Brown, blue, black
Outside color Grey Grey
Ext. diameter 7.8 mm 8.1 mm
Conductor Flexible CU Flexible CU
Isolation material PVC PVC
Amb. temperature • Flexible installation −5 to 70°C −5 to 70°C
• Non flexible installation −30 to 70°C −30 to 70°C
Cable parameter Capacity 161.50 pF/m N.A.
Inductance 0.583 µH/m N.A.
L/R 43.83 µH/Ω N.A.
Special cable