64 DKFD.PS.027.W3.02
SITRANS F M MAGFLO
8. Commissioning
Commissioning
8.4.8
Service mode
All previous settings are reinitialised when service mode is exited using the top up key.
The error system
The error system is divided into an error pending list and a status log list. Time is gained as days,
minutes and hours since the error has occurred.
The first 9 standing errors are stored in error pending. When an error is removed it is removed from
error pending.
The latest 9 errors are stored in the status log. When an error is removed it is still kept in status log.
Errors in status log is stored for 180 days.
Error pending and status log are accessible when enabled in the operator menu.
Menu detail
1) Standard
2) If digital output is set to
frequency