61
DKFD.PS.027.W3.02
SITRANS F M MAGFLO
8. Commissioning
Commissioning
8.4.3
Digital and relay outputs
Error level
Error number
8.4.2
Outputs
Digital output
Frequency
Proportional to flowrate
(Terminal 56, 57, 58)
The current output must be set off when not used.
Current output
Proportional to flowrate
(Terminal 31 and 32)
4 - 20 mA + alarm:
Current output gives the following mA, depending on what is selected as error level in basic settings.
Fatal: 1 mA, permanent: 2 mA, warning: 3 mA
Digital output
Pulse/volume
(Terminal 56, 57, 58)