SITRANS F M MAGFLO
DKFD.PS.027.W3.02
6. Installation of signal converter
Installation of signal conv.
49
6.3
Signal converter
Safety barrier
1. Fit the SENSORPROM
®
memory unit on the connection board supplied with the safety barrier.
The SENSORPROM
®
unit is delivered mounted in the terminal box of the sensor. The
connection board supplied with the signal converter is not used.
2. Mount the guide rails into the rack system as shown. Distance between guide rails is 20 TE.
Guide rails are supplied with the rack system and not with the signal converter.
3. Mount the connection board as shown. The mounting screw must be installed just in line with
the guide rails.
4. Connect the cables as shown under "Electrical connection", chapter 7.
5. Insert the signal converter and the safety barrier into the rack system.