Commissioning
6.3 Parameterizing the device
70 Equipment Manual, 09/2022, L1V30415168B-03
Selection
Range
Factory setting
Pulses per unit
(only for: energy
pulse)
Number of pulses, energy unit (kWh/kvarh), that are exported.
Range: 1 to 4000
1
Output pulse
divider
(only for: energy
pulse)
Range: 1; 10; 100; 1000
1
Pulse duration
(only for: energy
pulse)
Duration of the energy pulses
Range: 30 ms to 500 ms
100 ms
Time out of the
digital output
(only for: remote
controlled)
Switches the output on expiry of the set time, if the output is no longer
addressed.
Range: 1 s to 18000 s
0 s
Group
assignment
(only for: remote
controlled)
Digital outputs of networked devices can be grouped together to form a switching
group or various switching groups. This enables multiple digital outputs, which
may be distributed over multiple power monitoring devices, to switch
simultaneously.
This parameter shows the "switching group" on the bus to which the digital
output is assigned.
Range: 1 to 99
0

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SENTRON PAC3200T and is the answer not in the manual?

Siemens SENTRON PAC3200T Specifications

General IconGeneral
BrandSiemens
ModelSENTRON PAC3200T
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals