EasyManua.ls Logo

Siemens SENTRON VL Series

Siemens SENTRON VL Series
286 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Data library
8.7 Formats
3WL/3VL circuit breakers with communication capability - PROFIBUS
266 System Manual, 03/2011, A5E01051353-02
Table 8- 57 Format (107) "Switched-off I2t values"
Byte Bit Meaning
0 Phase L1 (unsigned long)
4 Phase L2 (unsigned long)
8 Phase L3 (unsigned long)
12 Phase N (unsigned long)
The table below shows the format (108) "Number of poles" that specifies the number of
protected poles for the main circuit.
Table 8- 58 Format (108) "Number of poles"
Byte Value Meaning
0 1 3-pole
0 2 4-pole (with N-conductor)
The table below shows the format (111) "Switch position DI" that also distinguishes the
switch position of the digital input module between Module 1 and 2.
Table 8- 59 Format (111) "Switch position DI"
Byte Value Meaning
0 1 Parameter set switching (Module #1)
0 2 6 x digital inputs (Module #2)
The table below shows the format (119) "Switch position DO" that specifies which output
block is selected with which delay.
Table 8- 60 Format (119) "Switch position DO"
Byte Value Meaning
0 0x01 Module #1 trip instantaneous
0 0x02 Module #1 trip delayed 200 ms
0 0x03 Module #1 trip delayed 500 ms
0 0x04 Module #1 trip delayed 1 s
0 0x05 Module #1 trip delayed 2 s
0 0x06 Module #2 alarm instantaneous
0 0x07 Module #2 alarm delayed 200 ms
0 0x08 Module #2 alarm delayed 500 ms
0 0x09 Module #2 alarm delayed 1 s
0 0x0A Module #2 alarm delayed 2 s
The table below shows the format (121) "Control DO outputs" for controlling the outputs of
the digital output modules with rotary coding switches.

Table of Contents

Other manuals for Siemens SENTRON VL Series

Related product manuals