Range -32768 to 32767
For example, Modbus value is:
1000 = 100 kVAr for 230-V sensor
1000 = 1000 kVAr for 3.25/√3 sensor, for 100/√3 sensor, and for 400/√3 sensor
i
i
NOTE
The reactive power in phase 1 (register address 1024) will saturate after 32767.
Power Factor Phase 1 (Cos φ )
(Address 1025) This register contains the power factor phase 1 (cos φ) in 1/1000.
Bit 15 14 13 12 11 10 9 8
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
Bit 7 6 5 4 3 2 1 0
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Format 16-bit signed integer
Unit 1/1000
Range -1000 to 1000
Frequency Phase 1
(Address 1026) This register contains the frequency phase 1 in 1/100 Hz.
Bit
15 14 13 12 11 10 9 8
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
Bit 7 6 5 4 3 2 1 0
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Format 16-bit unsigned integer
Unit 1/100 Hz
Range 0 to 65535
For example, if Modbus value is:
5020 = 50.2 Hz
Apparent Power Phase 2
(Address 1027) This register contains the apparent power phase 2.
Refer to Apparent Power Phase 1, Page 133.
Active Power Phase 2
(Address 1028) This register contains the active power phase 2.
Refer to Active Power Phase 1, Page 134.
Reactive Power Phase 2
(Address 1029) This register contains the reactive power phase 2.
Refer to Reactive Power Phase 1, Page 134.
Power Factor Phase 2
(Address 1030) This register contains the power factor phase 2.
Refer to Power Factor Phase 1 (Cos φ ), Page 135.
Modbus Registers
B.5 Register-Type Data – Input Registers
SICAM, Feeder Condition Monitor, Manual 135