Apparent Power Phase 3
(Address 1031) This register contains the apparent power phase 3.
Refer to Apparent Power Phase 1, Page 133.
Active Power Phase 3
(Address 1032) This register contains the active power phase 3.
Refer to Active Power Phase 1, Page 134.
Reactive Power Phase 3
(Address 1033) This register contains the reactive power phase 3.
Refer to Reactive Power Phase 1, Page 134.
Power Factor Phase 3
(Address 1034) This register contains the actual power factor phase 3.
Refer to Power Factor Phase 1 (Cos φ ), Page 135.
Power-Flow Direction of Phase I
1
(Address 1035) This register contains the power-flow direction of phase I
1
.
Bit 15 14 13 12 11 10 9 8
Not used Not used Not used Not used Not used Not used Not used Not used
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
Bit 7 6 5 4 3 2 1 0
Not used Not used Not used Not used Not used Not used DIR B DIR A
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Format 16-bit unsigned integer
Unit –
Bit type DIR A = Power-flow direction: A
DIR B = Power-flow direction: B
Data 01 = Power-flow direction A
10 = Power-flow direction B
11 = Power-flow direction is not determined
Power-Flow Direction of Phase I
2
(Address 1036) This register contains the power-flow direction of phase I
2
.
Refer to Power-Flow Direction of Phase I
1
, Page 136.
Power-Flow Direction of Phase I
3
(Address 1037) This register contains the power-flow direction of phase I
3
.
Refer to Power-Flow Direction of Phase I
1
, Page 136.
3-Phase Active Power
(Address 1038) This register contains the 3-phase active power.
Bit
15 14 13 12 11 10 9 8
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
Bit 7 6 5 4 3 2 1 0
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Modbus Registers
B.5 Register-Type Data – Input Registers
136 SICAM, Feeder Condition Monitor, Manual
E50417-H8940-C580-A4, Edition 03.2019