1.7 Environmental Specifications
Operating
temperature
0°
C to 60
°
C (32
°
F to 140
°F)
Storage temperature
–40°
C to 70
°
C (–40
°
F to 158
°F)
Relative humidity
5% to 95% noncondensing
Vibration
Sinusodial
IEC 68–2–6, T
est Fc;
0.15 mm peak-to-peak, 10–57 Hz;
1.0 g, 57–150 Hz
Random
NAVMA
T P–9492 or IEC 68–2–34, T
est
Fdc with 0.04 G/Hz, 80–350 Hz and
3db/octave rolloff 80–20 Hz and
350–2 kHz, at 10 min/axis
Impact shock
IEC 68–2–27, T
est Ea; Half Sine, 15 g, 1
1 ms
Electrostatic discharge
IEC 801, Part 2, Level 4 (15 kV)
Noise immunity (conducted)
IEC 801, Part 4, Level 3
MIL–STD–461B CS01, CS02, CS06 IEC
255–4,
Appendix
E EEC 4517/79 Com
(78) 766 Final, Part 4 IEEE 472,
2.5 kV
Noise immunity (radiated)
IEC 801, Part 3, Level 3
MIL–STD–461B RS01, RS02
Agency Approvals: U.L., CSA listing