EasyManua.ls Logo

Siemens SIMATIC 505 - Definitions of Constants; Constant 1; Constant 2

Siemens SIMATIC 505
150 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Software Interface
2-13
2.6.1
The
constants (V
-memory locations 1–14 of each of the five profiles) are
defined in the following paragraphs.
2.6.2
Constant 1 contains the module sample rate for this profile: 0–32767 in
PLC = 0–32.767 ms. The normal value is 5000 or 5 ms; the minimum value
is 1500 or 1.5 ms.
2.6.3
For all profiles except pack and hold, constant 2 contains the maximum
profile time to transition: 0–32766 in PLC = 0–327660 ms or 327.66 seconds.
For example, 325 = 3250 ms or 3.25 seconds. Note that 32767 = infinite
time.
For pack and hold profile, constant 2 contains the minimum position of the
injection ram to transition (end): 0–32000 in PLC = 0–10 V input. For
example, 16000 = 5 V or 50 percent of scale.
2.6.4
For clamp close profile, constant 3 contains the lock-over velocity value (one
of three lock-over variables stored in constants 3, 4, 5). The lock-over
velocity provides a clamp lock-over feature for toggle machines by producing
an additional burst of hydraulic flow and/or pressure for a specific amount
of time at the end of the clamp close profile to force the toggle mechanism
over center
.
If the lock-over time (constant 5) is not zero, the lock-over velocity feature
will be activated, providing hydraulic flow and pressure for a specified time
after completion of the clamp close profile, whether by position: 0–32000 in
PLC = 0–10 V output. For example, 8000 = 2.5 V or 25 percent of scale.
For injection and pack and hold profiles, constant 3 contains the maximum
pressure value required to transfer from this profile. T
o disable constant 3,
load 32767 or you can inhibit pressure transfer at different steps by using
constant 10 Bits 14 –16. For plasticate profile, constant 3 contains the cure
timer value.
Y
ou can specify a pressure threshhold before you enter a clamp open profile.
Download table 179 (clamp open constant 3) specifies a value for comparison
to channel 4. If a current channel 4 value is equal to or less than the value
at download table 179, a clamp open profile is started.
Definitions of
Constants 1–14
Constant 1
Constant 2
Constant 3

Table of Contents

Other manuals for Siemens SIMATIC 505

Related product manuals