EasyManua.ls Logo

Siemens SIMATIC 505 - PLC Output Words: PLC Data; Module; WY5 = Pointer to V-Memory; WY6 = Pointer to V-Memory

Siemens SIMATIC 505
150 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Software Interface
2-9
2.4 PLC Output Words: PLC Data Module
2.4.1
WY5
contains the V
-memory start location for the profile download of the
data table to the module. For example, WY5 = 101 means download table
begins at V
-101.
Zero is not a valid value.
Max value = PC V
-memory max—300 or 65315 max.
2.4.2
WY6 contains the V
-memory start location for the upload of the process
variable data table to the PLC. For example, WY6 = 400 means the upload
table begins at V
-400.
Zero is not a valid value.
Max value = PC V
-memory max—100 or 65440 max.
2.4.3
WY7 contains the module mode control value as follows:
An integer value of 1
121 in WY7 = run and enable special function (SF)
transfers. All other values = disable run mode and lock out SF transfers.
An integer value of 5000 in WY7 = the software revision display
command that forces WX1 to display the current software revision (Rev
.)
number.
2.4.4
A transition from zero to a non-zero value in WY8 is required to execute a
profile. A transition from a non-zero to a zero value is required to reset an
error condition and to set up to start another cycle.
For example, the binary value 1
11
1 1000 0000 0000 in WY8 tells the module
to run a complete cycle with everything in closed loop mode. The module
looks only at the first 5 bits of the WY8 word for the start, stop, and reset
functions. Therefore, only the first 5 bits need to be zero to stop or reset this
cycle.
WY5 = Pointer to
V-memory
WY6 = Pointer to
V-memory
WY7 =
Module
Mode Control
WY8 = Start Cycle

Table of Contents

Other manuals for Siemens SIMATIC 505

Related product manuals