Discrete Outputs
4-3
4.2 Specifications
Discrete
Output Specifications
Item Value
Total output current (all outputs on)
0.90 A (40
°C)
0.75 A (60
°C)
Maximum current per output
0.50 A (40
°C)
0.40 A (60
°C)
Rated voltage 15 to 24 VDC
Operating voltage range 12 to 30 VDC
Temporary overload 2.0 A for 1 ms
Maximum on-state voltage drop 0.5 VDC
Maximum off-state leakage current
0.2 mA
Kickback protection diode
Maximum delay time through module
(with 5 mA minimum load)
1 ms on to off
1 ms off to on
Type of outputs non-latching, unprotected
Output fuse rating
1amp, 125 V
, normal blow,
5x20 mm