Configuration
4.5 Configuration in STEP 7 Basic
CP 1243-8 IRC
66 Operating Instructions, 02/2018, C79000-G8976-C385-03
DNP3
The CP acknowledges a request of the master with its reply frames.
The acknowledgment of frames that the CP sends to the master is configured with the
parameters "Connection confirmation" and "Monitoring time for unsolicited frames", see
section Transmission settings DNP3 (Page 75).
IEC
The CP acknowledges a request of the master with its reply frames.
The acknowledgment of frames that the CP sends to the master is configured with the
parameters "Send sequence number" and "Receive sequence number", see section
Transmission settings - IEC (Page 77).
Open User Communication
The successful sending and receipt of frames is indicated by status displays of the program
blocks.
With TCP segments, the protocol-specific acknowledgement mechanisms are used.
4.5
Configuration in STEP 7 Basic
Requirement
The complete configuration of the CP in STEP 7 Basic is only possible after configuring in
STEP 7 V5 (see above).
Overview of configuration in STEP 7 Basic
Follow the steps below when configuring:
1. Create a STEP 7 project.
2. Insert the S7-1200 CPU for the SIMATIC station.
3. Create the PLC tags required for the data points in the CPU, see also point 7.
4. Select the CP 1243-8 in the catalog and set the firmware version of the CP in the catalog
using the "Version" drop-down list.
To use the CP with the functions of a TIM 3V-IE Advanced in a SINAUT ST7 system,
select version V2.1.
In all other cases, select a version with V3.0 or higher.
5. Insert the CP selected in the catalog into the stations.
6. Importing configuration data from STEP 7 V5:
The function is supported only for the CP with firmware version V2.1. If you are using the
CP with firmware version V3, continue at step 7.
If you are using the CP with the functions of a TIM 3V-IE Advanced for a SINAUT ST7
system, in the parameter group "Partners" import the configuration data of the TIM from

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-1200 CP 1243-8 IRC and is the answer not in the manual?

Siemens SIMATIC S7-1200 CP 1243-8 IRC Specifications

General IconGeneral
Product TypeCommunication Processor
SeriesSIMATIC S7-1200
ModelCP 1243-8 IRC
Data Transfer Rate10/100 Mbps
Power Supply24 V DC
MountingDIN rail
Dimensions (W x H x D)45 mm x 100 mm x 75 mm
Digital Inputs Quantity0
Digital Outputs Quantity0
Supported ProtocolsISO-on-TCP
InterfaceEthernet
IP AddressingStatic, DHCP
ConfigurationSTEP 7 Basic/Professional
Operating Temperature-20°C to +60°C
WeightApprox. 200 g