Configuration
4.9 Serial interface
CP 1243-8 IRC
84 Operating Instructions, 02/2018, C79000-G8976-C385-03
4.9.5
Advanced options
4.9.5.1
Dedicated line
Settings dedicated line
Only the configurable parameters are explained.
Settings serial interface
Interface standard
Standard of the serial interface: RS-232 / RS-485
Select the following value:
RS-232
When a modem with an RS-232 interface is connected to the interface of the CP
RS-485
When a modem with an RS-485 interface is connected
With parallel connection of several modems to the interface (star-shaped network).
Not relevant for the CP with the Network node type "Station".
RS-485 termination
Enable the option when connecting a terminating resistor for the RS-485 bus when a star-
shaped network is connected.
Number of spontaneous frames
Number of spontaneous frames
Only for interfaces with the Network node type "Station" / "Node station".
The parameter decides after how many frames the master station has the opportunity of
transferring its pending frames to the station. As maximum, the configured number of
spontaneous frames that are pending at the time of the first call frame are transferred.
Default setting: 200. Permitted range: 0...255
If 0 (zero) is set, all spontaneous frames are sent at the call.
Connection
Extra transmission time
Time offset (s) with slow networks to prevent premature stopping of connection
establishment.
Default setting: 10. Permitted range: 0...65535. If 0 (zero) is set, the function is disabled.
Usually in dedicated line networks the value is 0:

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-1200 CP 1243-8 IRC and is the answer not in the manual?

Siemens SIMATIC S7-1200 CP 1243-8 IRC Specifications

General IconGeneral
Product TypeCommunication Processor
SeriesSIMATIC S7-1200
ModelCP 1243-8 IRC
Data Transfer Rate10/100 Mbps
Power Supply24 V DC
MountingDIN rail
Dimensions (W x H x D)45 mm x 100 mm x 75 mm
Digital Inputs Quantity0
Digital Outputs Quantity0
Supported ProtocolsISO-on-TCP
InterfaceEthernet
IP AddressingStatic, DHCP
ConfigurationSTEP 7 Basic/Professional
Operating Temperature-20°C to +60°C
WeightApprox. 200 g

Related product manuals