Configuration
4.9 Serial interface
CP 1243-8 IRC
Operating Instructions, 02/2018, C79000-G8976-C385-03
85
Time options
RTS/CTS delay time
The RTS/CTS delay (ms) can be required when a modem is connected via an RS-485
interface.
Default setting: 0. Permitted range: 0...65535
Value 0
After setting the RTS signal, (turn transmitter on) transmission only starts when the
CTS signal (Clear To Send) was set by the modem.
Value > 0
Transmission is not delayed until the CTS signal of the modem.
After the RTS signal has been set, transmission is delayed for the configured time and
then started immediately.
Send delay time
The send delay time (ms) is used only when the clear to send (CTS signal) comes from
the modem (RTS/CTS delay time = 0).
As soon as the CTS signal comes from the modem, the send delay time is started.
Sending starts after the time has elapsed.
Default setting: 0. Permitted range: 0...65535
Polling monitoring time
Only for interfaces with the Network node type "Station" / "Node station".
The latest time (s) after which a CP expects to be polled. When this time has expired, the
CP sends a message to its local CPU indicating that the master station is disrupted.
Default setting: 0. Permitted range: 0...65535.
Parameters configured:
After the configured time elapses, the CP sends a message to the local CPU.
Parameter not configured at a transmission speed of 9600 bps:
After 4 seconds without frame traffic, the CP outputs a message.
Parameter not configured at a transmission speed of 1200 bps:
After 32 seconds without frame traffic, the CP outputs a message.
Max. allowed disruption time
Tolerance time (s) for a detected connection disruption.
If there is still a disruption on the connection when the set time has elapsed, the
disruption is signaled to all connection partners of the disrupted station.
Default setting: 0. Permitted range: 0...255. If 0 (zero) is set, the function is disabled.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-1200 CP 1243-8 IRC and is the answer not in the manual?

Siemens SIMATIC S7-1200 CP 1243-8 IRC Specifications

General IconGeneral
Product TypeCommunication Processor
SeriesSIMATIC S7-1200
ModelCP 1243-8 IRC
Data Transfer Rate10/100 Mbps
Power Supply24 V DC
MountingDIN rail
Dimensions (W x H x D)45 mm x 100 mm x 75 mm
Digital Inputs Quantity0
Digital Outputs Quantity0
Supported ProtocolsISO-on-TCP
InterfaceEthernet
IP AddressingStatic, DHCP
ConfigurationSTEP 7 Basic/Professional
Operating Temperature-20°C to +60°C
WeightApprox. 200 g

Related product manuals