Configuration
4.8 Ethernet interface
CP 1243-8 IRC
Operating Instructions, 02/2018, C79000-G8976-C385-03
75
4.8.5.3
Transmission settings - ST7
Transmission settings
Send conditional spontaneous frames as blocks
Indicates the form of transfer of data frames with the transmission mode "Conditional
spontaneous".
Option enabled
Several items of data are collected and only sent when a frame has reached
maximum capacity.
Option disabled
The data is sent spontaneously as individual frames.
The transfer mode (Spontaneous / Conditional spontaneous) of a frame is set in the
"Trigger" tab of the data point.
Max. allowed disruption time
Tolerance time (s) for a detected connection disruption.
If there is still a disruption on the connection when the set time has elapsed, the
disruption is signaled to all accessible connection partners of the disrupted station.
Default setting: 0. Permitted range: 0...255. If you enter 0 (zero), the function is disabled.
4.8.5.4
Transmission settings DNP3
Transmission settings DNP3
Disturbance bit
The disturbance bit can be used as bit 1.6 (IIN1.6) of the "Internal Indication Bytes" to
indicate to the master when the CPU is in STOP mode.
Max. time between Select and Operate
Max. duration (seconds) between Select and Operate. For a Select command to be
transferred to the CPU and to take effect, no other frame may be sent to the station
between Select and Operate.
Permitted range: 1..65535
Default setting: 1
Frame repetitions
Number of frame repetitions at the Data Link Layer if no acknowledgement is received
from the master.
Permitted range: 0 ... 255
Default setting: 0
If you enter 0 (zero), the function is disabled.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-1200 CP 1243-8 IRC and is the answer not in the manual?

Siemens SIMATIC S7-1200 CP 1243-8 IRC Specifications

General IconGeneral
Product TypeCommunication Processor
SeriesSIMATIC S7-1200
ModelCP 1243-8 IRC
Data Transfer Rate10/100 Mbps
Power Supply24 V DC
MountingDIN rail
Dimensions (W x H x D)45 mm x 100 mm x 75 mm
Digital Inputs Quantity0
Digital Outputs Quantity0
Supported ProtocolsISO-on-TCP
InterfaceEthernet
IP AddressingStatic, DHCP
ConfigurationSTEP 7 Basic/Professional
Operating Temperature-20°C to +60°C
WeightApprox. 200 g