Configuration
4.8 Ethernet interface
CP 1243-8 IRC
76 Operating Instructions, 02/2018, C79000-G8976-C385-03
Connection confirmation
Condition for the CP to request a connection confirmation from the master (never,
always, only with segmented frames).
Connection monitoring time
Time (in seconds) within which an acknowledgement is expected from the master.
Permitted range: 0...65535
Default setting: 2
If you enter 0 (zero), the function is disabled.
Transfer mode "Unsolicited"
Transfer mode for events
Spontaneous
Event frames are transferred immediately.
Conditional spontaneous
Event messages are only sent when spontaneous frames are sent or the partner
establishes the connection.
Max. number of unsolicited frames
Maximum number of repetitions of unsolicited frames if no acknowledgement is received
from the communications partner .
Permitted range: 0...255
Default setting: 3
Monitoring time for unsolicited frames
Time (in seconds) within which an acknowledgement of unsolicited frames is expected
from the master.
Permitted range: 1...65535
Default setting: 5
Buffer for class 1 / 2 / 3 events
Here, for each of the three event classes you specify the number of events after which
the stored events are sent to the communications partner.
Permitted range: 1 ... 255.
Delay time class 1 / 2 / 3 events
Here, for each of the three event classes you specify the maximum time in seconds the
events can be stored in the send buffer before they are sent to the communications
partner.
Permitted range: 0 ... 65535
If you enter 0 (zero), the function is disabled.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-1200 CP 1243-8 IRC and is the answer not in the manual?

Siemens SIMATIC S7-1200 CP 1243-8 IRC Specifications

General IconGeneral
Product TypeCommunication Processor
SeriesSIMATIC S7-1200
ModelCP 1243-8 IRC
Data Transfer Rate10/100 Mbps
Power Supply24 V DC
MountingDIN rail
Dimensions (W x H x D)45 mm x 100 mm x 75 mm
Digital Inputs Quantity0
Digital Outputs Quantity0
Supported ProtocolsISO-on-TCP
InterfaceEthernet
IP AddressingStatic, DHCP
ConfigurationSTEP 7 Basic/Professional
Operating Temperature-20°C to +60°C
WeightApprox. 200 g

Related product manuals