Configuration
4.8 Ethernet interface
CP 1243-8 IRC
Operating Instructions, 02/2018, C79000-G8976-C385-03
73
If the router can be reached via a dynamic IP address, there must be at least a reachable
DNS server in the network.
●
The port number is preset. If necessary, you can change the port number. Note that the
port number of both partners must be identical. The port number cannot be configured for
the station.
Default setting: 26382. Permitted range: 1024...65535
●
If the router should be reachable using the host name enter it here.
●
Here, enter the addresses of the DNS servers in the subnet.
The description applies to the parameter group of an Ethernet interface with the Network
node type "Master station". The parameter group is disabled for the CP.
●
Monitoring time (minutes) for the MSC connection
– Behavior of the master station:
If there is no data traffic between the MSC master and station within the monitoring
time, the MSC master sends a sign of life frame to the station.
– Behavior of the master station:
If no sign of life message comes from the MSC master within the monitoring time, the
station sets all subscribers reachable via MSC as disrupted.
Default setting: 10. Permitted range: 0...65535
If you enter 0 (zero), the function is disabled.
●
If the option is enabled, the MSC master passes the monthly transferred data volume of
the stations to online diagnostics.
The parameter group is only active when the setting of the Network node type of the
interface is "Station" or "Node station".
●
Activate security protocol MSCsec
If the option is enabled, the secure version of the MSC protocol "MSCsec" is used.
●
Time (h) after which the secret key is renewed between the MSC station and master
station.
Default setting: 0. Permitted range: 0...255