Prerequisites and communication setup
2.3 Starting the SIMATIC Automation Tool
SIMATIC Automation Tool V2.1 user guide
18 Manual, V2.1.1 07/2016, A5E33042676-AC
2.3
Starting the SIMATIC Automation Tool
Options for starting the SIMATIC Automation Tool:
Double-click the SIMATIC Automation Tool shortcut icon on your desktop.
Use the Windows Start button.
Click the Windows start button and "All Programs".
Click the "Siemens Automation" folder, then the "SIMATIC Automation Tool" folder,
and finally "Automation Tool".
Start the Windows command prompt (cmd.exe) and enter the executable file name and
optional project parameter.
AutomationTool.exe [projectname.sat].
2.4
CPU configuration requirements
Ethernet address configuration
If you want the SIMATIC Automation Tool to set the IP address or PROFINET name of a
CPU, then your TIA portal project must enable these actions in the CPU device
configuration. Use the TIA portal to view and modify a program's IP protocol setting, as
shown in the following S7-1200 example.
IP address and PROFINET name change
It Is
possible
for CPUs directly connected to the network that is connected to the
SIMATIC Automation Tool (including connection through an Ethernet switch).
It is
not possible
for CPU's with an indirect connection through a CP module, or a CPU's
secondary Ethernet port when the direct connection is to the primary Ethernet port.
It is
not possible
for CPU's on another network with a connection to the SIMATIC
Automation Tool that passes through an IP address router.

Table of Contents

Other manuals for Siemens SIMATIC S7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7 and is the answer not in the manual?

Siemens SIMATIC S7 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC S7
CategoryController
LanguageEnglish

Related product manuals