System runtime
The entire system runtime is displayed in CU parameter p2114.
r2114[0] indicates the system runtime in milliseconds. After reaching 86,400,000 ms (24
hours), the value is reset.
r2114[1] indicates the system runtime in days.
The counter value is saved when the power is switched off. After the drive unit has been
switched on, the counter continues to run with the value stored when the power was last
switched off.
As a result, the drive displays the system runtime from 00:00:00 on 01/01/1992 in both the
alarm window in SIMOTION SCOUT and the diagnostic buffer for entries.
If faults and alarms need to be "time-stamped" on the basis of a time of day, "Time-stamp
operating hours" needs to be changed to "Time-stamp UTC format" as described below.
Requirements
A telegram 39x is required for the time synchronization. If the automatic PROFIdrive telegram
setting is selected for the Control Unit, this telegram is used automatically (see Section
Accessing the drive wizard (Page 146), Standard/Automatic setting).
If the telegrams are specified manually, telegram 39x must be set up. See Section Message
frame configuration (Page 195)
So that drive units can be synchronized with the SIMOTION time, they must support telegram
39x and the UTC (coordinated universal time) time format.
For precise time synchronization, the drive unit must also be operated via an isochronous bus
on SIMOTION.
The SINAMICS Integrated with SIMOTION D is always connected isochronously.
The following Control Units support time synchronization:
SINAMICS Integrated of the SIMOTION D410‑2
SINAMICS S120 CU310, CU310‑2, CU320, CU320‑2 Control Units connected via
PROFIBUS or PROFINET
SINAMICS S110 Control Units CU305, connected via PROFIBUS or PROFINET
(precondition: as from SCOUT V4.4)
Commissioning (software)
7.4 Additional information on configuring the SINAMICS Integrated
SIMOTION D410-2
174 Commissioning and Hardware Installation Manual, 01/2015

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOTION D410-2 DP and is the answer not in the manual?

Siemens SIMOTION D410-2 DP Specifications

General IconGeneral
BrandSiemens
ModelSIMOTION D410-2 DP
CategoryController
LanguageEnglish

Related product manuals